Ecolab Builds Continuous Coolant Monitoring Into a 3 MW CoolIT CDU
The CHx 3000 moves 4,500 liters per minute at 50 psi and reads coolant chemistry continuously from startup. A day after the launch, Ecolab named Siemens, Alfa Laval and Dassault Systèmes as partners around it.
Ecolab introduced the CoolIT CHx 3000 at the SC26 supercomputing conference in Chicago on Nov. 16, a 3 MW coolant distribution unit with the company's 3D TRASAR monitoring built in. It is the product Ecolab said it would bring to the show when it closed its acquisition of CoolIT Systems on July 2. On Nov. 17 the company added what it calls an open ecosystem of partners: Siemens for power distribution and automation, Alfa Laval for heat exchangers and flow components, and Dassault Systèmes for virtual-twin modeling.
"For too long, cooling hardware, fluid management and digital technology have operated separately," said Christophe Beck, Ecolab's chairman, president and CEO. "We're bringing them together to help our customers get more computing power, faster, while using less water and energy."
- Cooling capacity: 3 MW at a 3°C approach temperature difference, liquid to liquid
- Flow and head: 4,500 LPM at 50 psi
- Power draw: 75 kW
- Rack count: up to 18 racks at 190 kW each, per CoolIT
- Enclosure: IP54 with active enclosure cooling, for white or grey space
- Controls: Redfish, Modbus TCP/RTU, BACnet IP and Ethernet/IP among supported protocols; group control of up to 20 CDUs
- Redundancy: N+1 pumps, filters and sensors, plus a built-in automatic transfer switch
Eighteen racks at 190 kW add up to 3.42 MW, above the unit's 3 MW rating, a gap that would close if each rack rejects part of its heat to air, as direct-to-chip racks commonly do; CoolIT's page does not state the liquid share it assumes. The same page gives the maximum ambient as 45°C in its summary and 50°C in its feature list.
Glycol Drift That pH Missed
The built-in sensors continuously measure glycol concentration, pH, turbidity and conductivity, and track contaminants through differential pressure, according to a Nov. 10 CoolIT technical post. Readings feed the facility's building management system. Ecolab's laboratories tested more than 3,000 PG25 samples from customer cooling loops worldwide and found 32 percent had at least one parameter out of specification under OCP and ASHRAE limits.
The post describes one site where glycol fell from 24.5 percent to 22 percent over two months while pH and conductivity stayed within normal ranges. The loop also contained PVC parts substituted during a rushed commissioning, and corrosion progressed until the system had to be taken offline. At another site, continuous monitoring caught a 10 psi rise in differential pressure across the loop, traced to corrosive particulate that side-stream filtration had missed. Ecolab installation teams have also found loops running before a standalone monitor had power, the post says, a gap the integrated design removes because monitoring starts when the CDU does.
Partners Named a Day Later
Siemens and Ecolab plan an integrated power and cooling package for high-density AI loads, pairing Ecolab's CDU technology with Siemens power distribution and digital twin software. "The thermal and energy demands of AI workloads have made piecemeal data center architectures obsolete," said Peter Koerte, president of Siemens Smart Infrastructure. Alfa Laval is working with Ecolab on the next generation of CHx 3000 units, contributing its heat exchanger and flow component work. Separately, on the same day, Alfa Laval launched its CB450 brazed plate exchanger and named CDUs as a target application. Dassault Systèmes built the virtual twin Ecolab showed at SC26, which links technology cooling system and facility water system models and reports results as water per token and time to token capacity.
Why This Matters to Contractors
Ecolab's high-tech unit, which now includes CoolIT and Ovivo, is growing more than 25 percent a year and approaching $1.5 billion in 2026 annualized sales, with a target of $4 billion by 2030. That target rests partly on coolant service, the same work Vertiv bought when it paid about $1.0 billion for flushing and filtration firm PurgeRite. With 3D TRASAR wired into the CDU and reporting over BACnet or Modbus, a falling glycol reading becomes a BMS alarm during commissioning and after, and whoever holds the service contract has to answer it.
Sources
- Ecolab, "Ecolab Launches Premier Liquid Cooling Ecosystem to Shape the Industry's Most Efficient AI Infrastructure," Business Wire via Yahoo Finance, Nov. 17, 2026. finance.yahoo.com
- Ecolab, "Ecolab Unveils First-of-Its-Kind Integrated Cooling Platform to Unlock the Next Generation of AI; Heralds New Tech-driven Growth Phase," Nov. 16, 2026. coolitsystems.com
- CoolIT Systems, "CoolIT CHx 3000" product page. coolitsystems.com
- CoolIT Systems, "Protecting Your Compute Starts at the Coolant," Nov. 10, 2026. coolitsystems.com