Data Centers

Vertiv Adds Pod and Data Hall Systems to Its 800 VDC Power Line

The new PowerDirect 9000 and PowerNexus MV SST join the rack-level system Vertiv introduced in May. Each conversion point changes where the power train's waste heat lands, and the data hall option moves it outdoors into a liquid-cooled container.

Key TakeawayVertiv now offers 800 VDC conversion at three points in an AI data center: inside the rack, ahead of a row or pod, and at the medium-voltage connection for a whole hall. Pilot programs and technical validation with customers are under way, and the portfolio is on show at SC26 this week.

Vertiv on Nov. 17 added 800 VDC power systems sized for an AI compute pod and for a full data hall, filling out a line that began in May with the PowerDirect 5000 Power Rack. The Westerville, Ohio, company is showing the portfolio at the SC26 supercomputing conference, which runs Nov. 17-22, and said pilot programs and technical validation work with customers are under way.

The release treats 800 VDC as one path among several. "AC and DC architectures are expected to coexist," it says, and the three options let an operator bring DC in at the rack, the pod or the hall without converting an entire building. "The 800 VDC power train is not just a new power product or conversion methodology; it is a set of architectures and system designs," said Scott Armul, Vertiv's chief product and technology officer.

Conversion From the Rack Out to the Grid Connection

At the rack level, the PowerDirect 3000 is a 90 kW, 1U power shelf that sits inside the compute rack and steps 800 VDC down to 54 VDC for the compute trays at up to 98.5 percent peak efficiency. It can deliver 180 percent pulse power for 0.5 milliseconds. Conversion and energy storage move into a power rack alongside the IT rack, one power rack serving one or two IT racks, which Vertiv says frees 8 to 16 rack units for compute while the upstream AC plant stays in place. The same platform runs at ±400 VDC with minor hardware changes.

For a row or pod, the new PowerDirect 9000 Power Center converts 480 VAC to 800 VDC at 1.5 MW and feeds the rack shelves over PowerBar Track DC busway and tap-off boxes. It scales in 60 kW steps through 27 hot-pluggable power supply units. Backup comes from the EnergyCore Li5 battery cabinet, which connects straight to the DC bus and supplies 200 kW of continuous backup at up to 98 percent conversion efficiency, with as many as six cabinets sharing current in parallel. Vertiv pitches this version at colocation providers serving tenants on different GPU generations.

The data hall option is the PowerNexus MV SST, a 5 MW solid-state transformer that takes medium-voltage AC to 800 VDC in a single stage and drops two to three intermediate conversion steps from a conventional power train. One unit can carry a 4.8 MW super pod reference architecture without chaining, and its power flow is bidirectional.

Where the Conversion Heat Goes

Each stage that comes out of the power train is one less source of heat for the cooling plant to remove, and the three architectures put the remaining losses in different places. At its 98.5 percent peak, a fully loaded 90 kW shelf would turn roughly 1.35 kW into heat inside the IT rack, by HAN's arithmetic from Vertiv's figures, and a peak rating describes the best point on the load curve. At 98 percent, a 5 MW transformer running at capacity would shed at least 100 kW.

Vertiv's design keeps that 100 kW out of the white space. The PowerNexus unit is a containerized outdoor design with liquid cooling, and the release says moving conversion outside recovers indoor floor space for compute. The release gives no heat rejection capacity or coolant specification for the container, which a mechanical engineer sizing the site would need. Vertiv's companion announcement a day earlier described its ATLAS lab, where power and thermal equipment for AI pods are tested as one system.

Why This Matters to Contractors

Vertiv writes that 800 VDC "needs safety practices and service procedures purpose-built for DC operating environments, not adapted from legacy AC," and lists touch-proof busbars, midpoint grounding, ground-fault detection and arc-flash prevention among the protections designed into the line. In a liquid-cooled AI pod, crews servicing CDUs and manifolds work in the same rooms as that distribution, and the release places DC-specific service offerings under Vertiv Services. Kyle Keeper, senior vice president of Vertiv's power management business unit, said customers can "choose an approach that aligns with their existing infrastructure," so a retrofit hall keeping its AC plant and a new campus fed by outdoor transformers will present different work to the trades on the same product line.

Sources

  1. Vertiv Holdings Co, "Vertiv Advances 800 VDC Power Architectures to Support Growing AI Data Center Demands," PR Newswire, Nov. 17, 2026. prnewswire.com
  2. Vertiv Holdings Co, "Vertiv ATLAS Proves AI Infrastructure Ahead of Silicon," PR Newswire, Nov. 16, 2026. prnewswire.com
Data Centers > Power DistributionVertiv800 VDCDC PowerAI Data CentersSolid-State TransformersLiquid CoolingPower ConversionEnergy StorageSC26Data CentersAI