Danfoss Launches 233 kW CoolTrain 2 Valve Train for Rack Liquid Cooling
CoolTrain 2 is rated for up to 233 kW, about four times the 55 kW Danfoss quoted for the first CoolTrain in March.
Danfoss will introduce CoolTrain 2, a plug-and-play valve train rated for up to 233 kW of liquid cooling, at Supercomputing 2026 in Chicago, the company said Nov. 9. The unit connects and balances coolant flow to server racks through flexible hose and a stainless steel, pressure-independent smart control valve. Danfoss will show it at booth 4823 during the Nov. 16-19 conference.
The first CoolTrain, launched in March, was a factory-built subsystem linking a facility's technology cooling system loop to the racks. It shipped pressure-tested, cleaned to ISO 4406, pre-filled and sealed, with 1-inch connections, an AB-QM pressure-independent control valve and an optional NovoCon S actuator for telemetry. Danfoss rated it at 55 kW, for racks up to 65 kW at a 10 K temperature difference, with flow of 8.3 to 83 liters per minute.
Valves Sized for Four Times the Flow
Two new stainless steel valves, the e-QC and e-PC, electronically balance rack flows up to 333 liters per minute, or 88 gpm. The e-QC holds a constant flow and the e-PC holds a differential pressure. Both carry a UL-certified NovoCon M2 digital actuator that feeds data center infrastructure management systems.
The connection hardware grows too. A 2.5-inch version of the Danfoss Hansen FD83 quick-disconnect coupling delivers nearly twice the flow of the existing FD83 with lower pressure drop, the company said. DataCryo 7G crimp fittings are built for Danfoss's DataCryo DC394 and EHW194 hoses. The release lists no prices or ship dates.
"Danfoss combines three decades of liquid cooling expertise with one of the industry's broadest data center portfolios, helping customers address the challenges of AI-driven growth," said Peter Bleday, vice president of data center solutions at Danfoss Power Solutions. Danfoss experts Estela Nario and Atul Puranik will present on interoperability, cleanliness and traceability in liquid cooling at the conference's Exhibitor Forum on Nov. 18.
Why This Matters to Contractors
At the 10 K rise Danfoss used to rate the first CoolTrain, 333 liters per minute of plain water carries about 232 kW, almost exactly the CoolTrain 2 figure, which suggests the new rating is set by the valve's flow ceiling at that same temperature split. Propylene glycol mixtures common on technology cooling loops carry less heat per liter than water, so a loop running glycol or a tighter temperature difference would land below 233 kW per train.
Sources
- Danfoss, "Danfoss to showcase end-to-end solutions for AI-ready data centers at Supercomputing 2026," Nov. 9, 2026. danfoss.com
- ACHR News, "Danfoss Introduces Liquid Cooling Products for Data Centers," Nov. 11, 2026. achrnews.com
- TechAfrica News, "Danfoss Unveils CoolTrain to Accelerate Deployment of Liquid Cooling Systems," March 26, 2026. techafricanews.com
- Danfoss, "CoolTrain: Ready-built valve trains for direct-to-chip liquid cooling in data centers," eBrochure. assets.danfoss.com