Daikin Applied Publishes 60 MW Cooling Design for Nvidia Vera Rubin AI Factories
Liquid cooling carries 92 percent of the IT load and rack containment units carry the other 8 percent. Eight 10 MW oil-free Magnitude chillers back up dry coolers on the high-temperature loop. The design basis is an Ashburn, Va., summer of 103.6 F.
Daikin Applied has published a 60 MW reference design for cooling an AI data center built on Nvidia's DSX AI Factory Platform with Vera Rubin NVL72 racks, pairing oil-free magnetic-bearing chillers with dry coolers and leaving out cooling towers. The Minneapolis company announced the design, Reference Architecture D60-W Water-Cooled Chillers with Dry Coolers, on Nov. 10, and parent Daikin Industries posted the release on its global site the next day.
D60-W splits the IT load across six deployable units. Coolant distribution units on a high-temperature loop remove 92 percent of the heat. DDC Solutions S-Series rack containment units take the remaining 8 percent into a separate low-temperature water loop, and the company says operators can run air-cooled, liquid-cooled and hybrid racks side by side.
"A cooling decision at the rack carries implications for water temperatures, flow requirements, plant operation and heat rejection," said Karim Shalash, director of Data Center Solutions at Daikin Applied. "D60-W gives engineering teams a framework for working through those dependencies and developing a cooling architecture around the facility's operating requirements."
Supply Temperatures and Equipment Counts
The D60-W page on Daikin Applied's site goes well past the release. Facility liquid is supplied at 37 C (98.6 F) and returns at 47 C (116.6 F), while the rack side of the CDUs runs 41 C (105.8 F) supply and 51 C (123.8 F) return. The rack containment loop is supplied at 22 C (71.6 F).
Each deployable unit holds 128 racks and seven 2.3 MW CDUs, six on duty and one on standby, sized at a 4 C approach. The central plant for the high-temperature loop uses eight Magnitude WME-C Quad chillers of 10 MW each, with six on duty plus two redundant, with 21 dry coolers plus two spares. The low-temperature loop gets six 1.4 MW Magnitude WME-A single chillers, with four on duty and two redundant, and two dry coolers plus two spares. The chillers are offered with R-513A or R-515B.
Daikin used Ashburn, Va., as the weather basis, with a summer design dry bulb of 39.8 C (103.6 F), a mean coincident wet bulb of 28.1 C (82.6 F) and a winter dry bulb of minus 12.9 C (8.8 F).
- IT load: 60 MW across six deployable units, 92 percent liquid and 8 percent air
- Facility liquid: 98.6 F supply, 116.6 F return
- High-temperature plant: eight 10 MW Magnitude WME-C Quad chillers (6+2), 21+2 dry coolers
- Low-temperature plant: six 1.4 MW Magnitude WME-A chillers (4+2), 2+2 dry coolers
- Refrigerant options: R-513A or R-515B
- Heat rejection: dry coolers only, no cooling-tower makeup water
Three Modes Keyed to Dry Cooler Leaving Temperature
The plant chooses its mode by adding the economizer heat exchanger approach to the dry cooler leaving-fluid temperature. At or below the facility supply setpoint, it runs on dry cooling with the chiller compressors off, and during full economization the facility supply resets up to 41 C, which gives 45 C rack supply through the CDUs. Between that point and the 47 C facility return, a waterside economizer precools return water and the chillers trim the rest. Above 47 C the economizer is bypassed and the chillers carry the full load.
Daikin Applied's iDCM supervisory controls coordinate the rack units, CDUs, chillers and dry coolers, sharing load and run hours between machines as the plant moves from one mode to the next. The release argues that oil-free compressors suit a plant whose chillers, in suitable climates, sit in standby most of the year, since there are no oil heaters or pumps to keep running and no oil-related delay when a chiller restarts. RideThrough and RapidRestore are the company's features for riding through brief power disturbances and restarting after a shutdown.
Why This Matters to Contractors
Two parts of the D60-W plant are not yet for sale. Daikin Applied says its own CDU and data center dry cooler are still in development, with availability targeted for the second half of 2027, so a plant drawn to this design today would use another maker's CDUs and dry coolers or wait for Daikin's. Each deployable unit is also rated at 13.8 MW of thermal capacity against a 10 MW plant allocation, and the design notes that using the difference requires more plant capacity, which leaves room on the rack side for later density at the cost of added chillers and dry coolers.