Researchers Find Six Pre-Login Takeover Flaws in Current Danfoss AK-SM 800A Firmware

All six are stack-based buffer overflows reachable before login, found in under an hour of manual review. One sits in the session control layer that CERT-FR told operators to switch on. No CVE numbers have been assigned.

Key TakeawayDutch firm Midnight Blue reported six pre-authentication remote code execution flaws in Danfoss AK-SM 800A firmware up to and including 5.3.2, the latest release it tested. The firm says patching and Strict session control will not protect exposed units and that the only reliable step is to take the controllers off the open internet.

Danfoss AK-SM 800A refrigeration system managers running firmware through version 5.3.2 contain six vulnerabilities that let an attacker take full control without logging in, the Dutch security firm Midnight Blue said in a blog post that Dutch broadcaster NOS reported Nov. 11. Version 5.3.2 was the newest release when the firm did its testing. No CVE numbers have been assigned, and Midnight Blue is withholding technical details while it works through coordinated disclosure with Danfoss.

Researcher Carlo Meijer found the flaws, all stack-based buffer overflows, in less than an hour of manual review of firmware downloaded from Danfoss's public website. "On a scale of 1 to 10 I'm heading toward 10," he told NOS, in a translation of the Dutch. "This is very serious."

Belgium's Centre for Cybersecurity followed with a warning to operators headed "Immediate Action Required." Its website refused automated requests, so the full text could not be reviewed for this article.

A Bug Inside Strict Mode

Since software 4.0, Danfoss has shipped the AK-SM 800A with session control set to Strict by default, an authentication layer that fences most of the web interface off from anyone who has not signed in. France's CERT-FR listed enabling it among its October mitigations. Meijer found that the separate program enforcing it, sm_fcgi_app, has its own pre-login memory corruption bug, which he crashed with an oversized browser identification string against firmware that had Strict mode on.

The main application, sm_app, runs as root and was built without stack canaries or position-independent code, two exploit defenses that a compiler setting turns on. Midnight Blue also noted that Danfoss business units including Climate Solutions hold IEC 62443-4-1 certification for secure product development, and wrote that buyers should "realize exactly how little such certifications can say about the actual security posture of a product."

Persistence After a Factory Reset

The controllers do not use the secure boot features of their i.MX6 processor, the firm found. That would let an attacker who gains code execution leave an implant that survives a factory reset and firmware update, or push corrupt firmware that renders the unit permanently inoperable. "This could potentially lead to freezers being unavailable for days or longer while controllers get replaced," the post said. Reset and reconfigure was the standard recovery step after the October attacks in France.

Danfoss told NOS that a software update fixing two problems would come out later on Nov. 11, but did not say whether they were the ones Midnight Blue found. As of Nov. 12, the newest AK-SM 800A entry on the company's security advisory page was still the August 2025 notice for CVE-2025-41451 and CVE-2025-41452, fixed in version 4.3.1.

The Midnight Blue Findings at a Glance
  • Affected: AK-SM 800A, all versions up to and including 5.3.2
  • Flaws: six stack-based buffer overflows, reachable before login
  • Possible impact: full takeover as root, persistence after reset, permanent denial of service
  • Exposure: hundreds of Danfoss systems and more than 1,000 Copeland and Dixell controllers online, per Censys searches dated Nov. 10
  • Status: CVEs pending, details withheld during disclosure

Exposure Over Patching

Midnight Blue recommends against putting scarce staff time into patching these units or switching on Strict mode. "We consider it of paramount importance for defenders not to fall into the trap of considering risks sufficiently mitigated by applying patches," the firm wrote. Its fix is to reach controller management interfaces only through a VPN, a private APN or a tightly drawn, firewall-enforced IP allowlist, and it says broad geographic blocking falls short. The advice covers Copeland and Dixell controllers as well, and Eliwell units, which have not been targeted, also remain exposed in the hundreds.

The disclosure arrives a month after Claroty's Team82 showed an AI coding agent reproducing three older AK-SM 800A vulnerabilities and chaining two of them into root access in about 28 minutes, for roughly $6 in usage. Meijer's post stresses that the new bugs took "no AI" to find.

Why This Matters to Contractors

Meijer told NOS that installers sometimes insist the controllers sit directly on the internet so they can watch them remotely, and Midnight Blue's own checklist starts with a step a store's IT staff can miss: finding controllers reached through 4G modems that system integrators installed, which never appear on the owner's public IP ranges. The firm acknowledges that service agreements and insurance terms often require remote access, which is why it points to a VPN or private APN that keeps the service link alive while closing the open port.

Sources

  1. Midnight Blue, Carlo Meijer, "Don't bother patching: multiple remote code execution vulnerabilities in Danfoss AK-SM800A," November 2026. midnightblue.nl
  2. NOS, Joost Schellevis, "Onderzoekers slaan alarm om kritieke lekken in koelsystemen: 'Dit is ernstig'," Nov. 11, 2026. nos.nl
  3. Centre for Cybersecurity Belgium, "Warning: Six New Danfoss Vulnerabilities - Refrigeration Controllers at Risk - Immediate Action Required!" November 2026. ccb.belgium.be
  4. Danfoss, "Danfoss security advisories," accessed Nov. 12, 2026. danfoss.com
  5. Danfoss, "AK-SM 800A Series" software and product security page, accessed Nov. 12, 2026. danfoss.com
  6. Claroty Team82, "Firmware to Root in 30 Minutes: How AI is Changing Threat Intelligence," Oct. 13, 2026. claroty.com
Controls > CybersecurityCybersecurityDanfossAK-SM 800ASupermarket RefrigerationFirmwareRemote AccessMidnight BlueVulnerabilities